Automatic under Voltage Load Shedding and Automatic Switching of Bus Reactors for Mitigating Fault Induced Delayed Voltage Recovery

سال انتشار: 1396
نوع سند: مقاله ژورنالی
زبان: فارسی
مشاهده: 65

فایل این مقاله در 7 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

JR_SAIRAN-8-2_015

تاریخ نمایه سازی: 9 آبان 1402

چکیده مقاله:

This paper presents the application of automatic under voltage load tripping and switching of shunt reactors as counter measures for fault induced delayed voltage recovery (FIDVR). As dynamic behavior of loads has significant impact on simulating FIDVR, proper load modeling is also discussed in this paper. Simulations conducted on actual network show that the proposed load model is effectively able to simulate FIDVR. It also shown that automatic under voltage load shedding and switching of shunt reactors can be used as counter measures for reducing risk of voltage collapse or over voltage conditions that may take place following load tripping caused by FIDVR.

کلیدواژه ها:

Induction motor ، under voltage load shedding ، Bus reactor ، Air conditioner ، Fault induced delayed voltage recovery