Transient modeling of transmission lines components with respect to corona phenomenon and grounding system to reduce the transient voltages caused by lightning Impulse

سال انتشار: 1394
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 511

فایل این مقاله در 8 صفحه با فرمت PDF قابل دریافت می باشد

استخراج به نرم افزارهای پژوهشی:

لینک ثابت به این مقاله:

شناسه ملی سند علمی:

KBEI02_283

تاریخ نمایه سازی: 5 بهمن 1395

چکیده مقاله:

In this paper, the behavior of the grounding system at different frequencies has been investigated under lightning conditions with and without the corona phenomenon. Also using EMTP-RV software, a model of Corona with two different earth systems was constructed at the high voltage alternating current transmission line and the effect of soil resistance changes and corona pulses were shown in the voltage signals across the insulator and it was found that the corona phenomenon causes voltage signal attenuation and damping and increasing the wave front time ,also it has been shown that the high-frequency grounding system has a higher validity than the low-frequency grounding system

نویسندگان

Ebadollah Amouzad Mahdiraji

Graduate Student of Azad University, Sari, Iran

Nabiollah Ramezani

University of Science and Technology of Mazandaran, Behshahr, Iran