Controlling Cooling Water Quality by Hydrodynamic Cavitation
محل انتشار: نخستین همایش چیلر و برج خنک کن ایران
سال انتشار: 1389
نوع سند: مقاله کنفرانسی
زبان: انگلیسی
مشاهده: 2,562
فایل این مقاله در 11 صفحه با فرمت PDF قابل دریافت می باشد
- صدور گواهی نمایه سازی
- من نویسنده این مقاله هستم
استخراج به نرم افزارهای پژوهشی:
شناسه ملی سند علمی:
CHILLER01_035
تاریخ نمایه سازی: 17 اسفند 1388
چکیده مقاله:
An independent field study was conducted on a cooling tower system at an automotive manufacturing facility to evaluate the performance of a VRTX hydrodynamic cavitation device for disinfection, scaling, corrosion and heat transfer efficiency. The VRTX treatment enabled the cooling tower system to operate at higher cycles of concentration than those obtained while on the chemical program without adversely affecting scaling,
corrosion and heat-transfer efficiency. On average, water consumption was reduced ~10% and blowdown was reduced over 30%. The test results also showed that the VRTX treatment performed as well as the chemical treatment program that it replaced with regard to bacteria control without adding any chemicals. The bacteria population was maintained at equal to or less than bacterial levels obtained while on chemical treatment. No Legionella was detected during the study period
نویسندگان
Erfan Ziarifar
Islamic azad university of Mahshahr, Amir Kabir Petrochemical
Bijan Ghanavati
Scientific Board Member of Islamic Azad University, Mahshar Branch
behnam amini
Islamic Azad University, omidiyeh Branch
Farid taheri
Islamic Azad University, omidiyeh Branch
مراجع و منابع این مقاله:
لیست زیر مراجع و منابع استفاده شده در این مقاله را نمایش می دهد. این مراجع به صورت کاملا ماشینی و بر اساس هوش مصنوعی استخراج شده اند و لذا ممکن است دارای اشکالاتی باشند که به مرور زمان دقت استخراج این محتوا افزایش می یابد. مراجعی که مقالات مربوط به آنها در سیویلیکا نمایه شده و پیدا شده اند، به خود مقاله لینک شده اند :